Drop Down MenusCSS Drop Down MenuPure CSS Dropdown Menu

Sunday 20 September 2015

High-Voltage Surge Arresters


High-Voltage Surge Arresters



In safe and reliable

Lightning Arresters
protection of electrical equipments, surge arresters are the primary protection against atmospheric and switching over voltages. The typical lightning arrester has a high-voltage terminal and a ground terminal. When a lightning surge (or switching surge, which is very similar) travels along the power line to the arrester, the current from the surge is diverted through the arrester, in most cases to earth. If protection fails or is absent, lightning that strikes the electrical system introduces thousands of kilovolts that may damage the transmission lines, and can also cause severe damage to transformers and other electrical or electronic devices.
Different relevant standards exists for design and type tests like IEC 60099-4 , ANSI/IEEEC62.11 and other specific standards.


Lightning Arresters Applications.

1). Protection of AIS and GIS substation equipment
2). HVDC protection
3). Protection of series capacitor banks
4). Protection of cables
5). Protection of transmission lines
6). Polluted areas and areas with high seismic activities.

Types.

1). Silicone-housed surge arrester :-

A flexible type of arrester for line discharge class 2 to 5 and system voltage up to 550 kV.

2). Composite-housed surge arrester :-

A high strength arrester for line discharge class 3 to 5 and system voltage up to 800 kV.

3). Porcelain-housed surge arrester :-

A high strength arrester family for line discharge class 2 to 5 and system voltage up to 800 kV.

Other Types

Horn Gap Arresters

Lightning ArrestersHorn gap arresters are named for their two horn-shaped metal rods. These rods are arranged around a small air gap, and the distance between the two rods increases as they rise 
o two different wires: One attaches to the electrical line. Between it and the horn is a resistance and a choke coil. The resistance regulates the level of current allowed into the arrester at once, and the choke coil increases the reactivity of the arrester when transient frequency occurs. The other wire is connected to a ground, which siphons the excess electricity to the ground.

Multi-Gap Arresters

Multi-gap arresters are made from a series of metal cylinders. These cylinders are all insulated from one another as well as separated by air gaps. The first cylinder gets connected to the electrical line, while all of the other cylinders are attached to the ground through a series resistance, which gradually wears down the power of the current. Some of the gaps between the later cylinders have a shunt resistance that catches a surge when there is an excess of voltage.

Valve-Type Arresters

Valve-type arresters are commonly used in more high-powered electrical systems. They consists of two main parts: a series of spark gaps and a series of non-linear resistor discs. Valve-type arresters work when excessive voltage causes the spark gaps to touch, and the non-linear resisters carry the voltage into the ground. Once the surge of excess power ends, the resisters push the spark gaps apart.

Brief performance data of Typical Lightning Arresters








System voltage  kV  72 - 145 24 - 170 52 - 420 52 - 420  300 - 550 
Rated voltage kV 75 - 120  18 - 144  42 - 360  42 - 360 228 - 444 
Nominal discharge current kApeak 10 10  10  20  20
Line discharge class Class 2 3 4 4
Mechanical strength (SSL)  Nm 1 300  1 600 4 000 4 000 9 000


Building Blocks

The most important component for the surge arresters is the ZnO blocks, the varistors. Stacked in the center of the surge arrester, the varistor is the heart of the surge arrester. The varistor consist of a mix of zink oxide and other metallic powders that are blended and pressed into cylindrical blocks.

Typical type tests performed for different size of ZnO varistor.

Tests on ZnO blocks

Energy withstand test on all blocks - The blocks pass three energy test cycles with cooling in-between. In each cycle, the injected energy is far in excess of the single impulse energy capability.



Classification of all blocks

ZnOVisual inspection and classification of the blocks at 1 mA (d.c.) and 10 kA (8/20 μs) and the residual voltages are printed on each block together with a batch identification.

Accelerated life tests on samples

Here power losses after 1 000 hours is calculated from a test with shorter duration (approximately 300 hours) at an elevated temperature of 115 °C at 1.05 times Uc shall not exceed the losses at start of the test.

Impulse current tests on samples

Blocks are subjected to high current impulses (4/10 μs) and long duration current impulses (2 500 μs) of amplitudes verifying catalogue data.

Friday 18 September 2015

GET YOUR ELECTRONIC PROJECT/PCB DESIGNED BY US

GET YOUR ELECTRONIC PROJECT/PCB LAYOUTS DESIGNED BY US

GET YOUR ELECTRONIC PROJECT, PCB DESIGNED BY US

GET YOUR ELECTRONIC PROJECT/PCB DESIGNED BY US. EASILY COMPLETE YOUR ASSIGNMENTS, HOME WORKS OR SOLVE CRITICAL PROBLEMS. GET P-SPICE/TINA-PRO/ELECTRONIC WORKBENCH- SIMULATION DRAWINGS, PARTS LIST, PCB- PRINTED CIRCUIT BOARD DRAWINGS/LAYOUTS IN YOUR DESIRED FORMAT, ALL DRAFTED BY US.
JUST SEND YOUR QUESTIONS/ DRAWING/DESIGN REQUESTS WITH RELEVANT DATA TO US BY EMAIL.

TERMS & CONDITIONS. 
1). SEND YOUR QUESTIONS/ DESIGN REQUESTS WITH RELEVANT DATA TO US IN THIS EMAIL ID. bujadas@gmail.com

2). MENTION THE FORMAT OF DESIGN YOU REQUIRE, WHICH WILL BE SENT TO YOU BY RETURN EMAIL. (ONLY SOFT COPY OF DESIGN WILL BE PROVIDED BY US)

3).  AS PER YOUR DESIGN REQUEST, WE WILL ANALYZE, THE PROBLEM, AND EMAIL YOU, ABOUT THE CHARGE/COST OF THE JOB. TYPICAL CHARGES IS 100/- TO 500/-.

4). IF YOU AGREE, SENT YOUR CONFIRMATION, FOR PROCESSING THE REQUEST, BY EMAIL.

5). AS SOON AS WE RECEIVE YOUR CONFIRMATION, WE WILL SOLVE THE DESIGN REQUEST, SEND YOU A SNAPSHOT OF THE PARTS LIST/PCB LAYOUT/GRAPH/TEST DATA, BY EMAIL.

6). NOW IF YOU ARE SATISFIED, WITH THE DESIGN SOLUTION, THEN EMAIL US THE CHARGE/COST OF THE JOB, AS PREVIOUSLY AGREED, IN FORM OF AMAZON.IN GIFT CARD.

7). AS SOON AS WE RECEIVE VALID AMAZON.IN GIFT CARD-OF THE REQUIRED AMOUNT, WE WILL EMAIL, THE DESIGN, WITH COMPLETE SOLUTION TO YOU.

8). THANK YOU FOR YOUR CO-OPERATION.

9). CONTACT DETAILS.  bujadas@gmail.com

GET YOUR DRAWINGS DONE BY US

GET YOUR DRAWINGS DONE BY US

GET YOUR ENGINEERING DRAWINGS DRAWN BY US. EASILY COMPLETE YOUR ASSIGNMENTS, HOME WORKS OR SOLVE CRITICAL PROBLEMS. GET AUTO-CAD DRAWINGS IN YOUR DESIRED FORMAT, ALL DRAFTED BY US.
GET CIVIL/MECHANICAL ENGINEERING DRAWINGS IN DIFFERENT FORMATS e.g. PLAN, ELEVATION, SIDE, ISOMETRIC VIEW-SOLUTION FROM US. JUST SEND YOUR QUESTIONS/ DRAWING REQUESTS WITH RELEVANT DATA TO US BY EMAIL.

TERMS & CONDITIONS. 
1). SEND YOUR QUESTIONS/ DRAWING REQUESTS WITH RELEVANT DATA TO US IN THIS EMAIL ID. bujadas@gmail.com

2). MENTION THE FORMAT OF DRAWING YOU REQUIRED, WHICH WILL BE SENT TO YOU BY RETURN EMAIL. (ONLY SOFT COPY OF DRAWING WILL BE PROVIDED BY US)

3).  AS PER YOUR DRAWING REQUEST, WE WILL ANALYZE, THE PROBLEM, AND EMAIL YOU, ABOUT THE CHARGE/COST OF THE JOB. TYPICAL CHARGES IS 100/- TO 500/-.

4). IF YOU AGREE, SENT YOUR CONFIRMATION, FOR PROCESSING THE REQUEST, BY EMAIL.

5). AS SOON AS WE RECEIVE YOUR CONFIRMATION, WE WILL SOLVE THE DRAWING REQUEST, SEND YOU A SNAPSHOT OF THE COMPLETE DRAWING, BY EMAIL.

6). NOW IF YOU ARE SATISFIED, WITH THE DRAWING SOLUTION, THEN EMAIL US THE CHARGE/COST OF THE JOB, AS PREVIOUSLY AGREED, IN FORM OF AMAZON.IN GIFT CARD.

7). AS SOON AS WE RECEIVE VALID AMAZON.IN GIFT CARD-OF THE REQUIRED AMOUNT, WE WILL EMAIL, THE DRAWING, WITH COMPLETE SOLUTION TO YOU.

8). THANK YOU FOR YOUR CO-OPERATION.

9). CONTACT DETAILS.  bujadas@gmail.com

INDUCTANCE OF A CONDUCTOR DUE TO INTERNAL FLUX

INDUCTANCE OF A CONDUCTOR DUE TO INTERNAL FLUX



The inductance of a transmission line is calculated as flux linkages per ampere. If permeability µ is constant, sinusoidal current produces sinusoidally varying flux in phase with the current. The resulting flux linkages can then be expressed as a phasor λ, and

 If i, the instantaneous value of current, is substituted for the phasor I in above eq., then λ should be the value of the instantaneous flux linkages produced by i. Flux linkages are measured in weber-turns, Wbt.
To obtain an accurate value for the inductance of a transmission line, it is necessary to consider the flux inside each conductor as well as the external flux. Let us consider a long cylindrical conductor whose cross section is shown in Fig. We assume that the return path for the current in this conductor is so far away that it does not appreciably affect the magnetic field of the conductor shown. Then, the lines of flux are concentric with the conductor.
  
By Ampere's law the magnetomotive force (mmf) in ampere-turns around any closed path is equal to the net current in amperes enclosed by the path. The mmf equals the line integral around the closed path of the component of the magnetic field intensity tangent to the path and is given by,

Where, H = magnetic field intensity, At/m
s = distance along path, m
I = current enclosed, A
Note that H and I are shown as phasors to represent sinusoidally alternating quantities.
Let the field intensity at a distance x meters from the center of the conductor be designated Hx. Since the field is symmetrical, Hx is constant at all points equidistant from the center of the conductor. If the integration indicated in Eq. above is performed around a circular path concentric with the conductor at x meters from the center, Hx is constant over the path and tangent to it. We get,
Where, Ix is the current enclosed. Then, assuming uniform current density, 
  Where, I is the total current in the conductor. Then, we obtain,
 The flux density x meters from the center of the conductor is,
Where, µ is the permeability of the conductor.
In the tubular element of thickness dx the flux dφ is Bx times the cross-sectional area of the element normal to the flux lines, the area being dx times the axial length. The flux per meter of length is,
 The flux linkages dλ per meter of length, which are caused by the flux in the tubular element, are the product of the flux per meter of length and the fraction of the current linked. Thus,
Integrating from the center of the conductor to its outside edge to find λint, the total flux linkages inside the conductor, we obtain, 
  For a relative permeability of 1, µ = 4π X 10-7 H/m, and,

Hence, we have computed the inductance per unit length (henrys per meter) of a round conductor attributed only to the flux inside the conductor.
 

Thursday 17 September 2015

TYPES OF CONDUCTORS IN POWER TRANSMISSION SYSTEM

TYPES OF CONDUCTORS IN POWER TRANSMISSION SYSTEM


Symbols identifying different types of aluminum conductors are as follows:

AAC- All Aluminum Conductors.
AAAC- All Aluminum Alloy Conductors.
ACSR- Aluminum Conductor Steel Reinforced.
HTLS- High Temperature Low Sag.


In the early days of the transmission of electric power conductors were usually copper, but aluminum conductors have completely replaced copper for overhead lines because of the much lower cost and lighter weight of an aluminum conductor compared with a copper conductor of the same resistance. The fact that an aluminum conductor has a larger diameter than a copper conductor of the same resistance is also an advantage. With a larger diameter, the lines of electric flux originating on the conductor will be farther apart at the conductor surface for the same voltage. This means there is a lower voltage gradient at the conductor surface and less tendency to ionize the air around the conductor.
Ionization produces the undesirable effect called corona.



Aluminum-alloy conductors have higher tensile strength than the ordinary electrical-conductor grade of aluminum. ACSR consists of a central core of steel strands surrounded by layers of aluminum strands. ACAR has a central core of higher-strength aluminum surrounded by layers of electrical conductor grad e aluminum.
Alternate layers of wire of a stranded conductor are spiraled in opposite directions to prevent unwinding and to make the outer radius of one layer coincide with the inner radius of the next layer. Stranding provides flexibility for a large cross-sectional area. The number of strands depends on the number of layers and on whether all the strands are of the same diameter. The total number of strands in concentrically stranded cables, where the total annular space is filled with strands of uniform diameter is 7, 1 9, 37, 61, 91, or more.
Figure shows the cross section of a typical steel-reinforced aluminum cable (ACSR). The conductor shown has 7 steel strands forming a central core, around which there are two layers of aluminum strands. There are 24 aluminum strands in the two outer layers. The conductor stranding is specified as 24 Al/7 St, or simply 24/7. Various tensile strengths, current capacities, and conductor sizes are obtained by using different combinations of steel and aluminum.

TECHNICAL PARTICULARS OF ACSR 'PANTHER', 'ZEBRA' & 'MOOSE' CONDUCTOR.


1.Specification to which the finished conductor conforms: IS-398Part-II-1976
2.Purity of Aluminium Rods: 99.5% Minimum
3.Percentages of Carbon in steel wire/rods: 0.50 to 0.85 (Preferably 0.65%)
4.Purity of Zinc: 99.95%





UnitACSR 'Panther'ACSR 'Zebra'ACSR 'Moose'
5.Particulars of Aluminium strands



i)Diameter




a) Standardmm3.003.183.53

b) Maximummm3.033.163.55

c) Minimummm2.972.193.51
ii)Cross sectional area of standard diameter wiremm27.0697.9429.787
iii)Weight per Km




a) StandardKg19.1121.4726.45

b) MaximumKg
c) MinimumKg


iv)Minimum breaking load




a) Before strandingKN1.171.291.57

b) After strandingKN1.111.231.49
v)Maximum D.C. resistance at 200COhm/Km4.1073.6512.921
vi)Joints in strands of 12 wire Aluminium layer if any
No jointNo jointNo joint
6.Particulars of Steel strands



i)Diameter




a) Standardmm3.003.183.53

b) Maximummm3.063.213.60

c) Minimummm2.943.143.46
ii)Cross sectional area of standard diameter wiremm27.0697.9429.787
iii)Weight per Km




a) Standardmm55.1361.9576.34

b) Maximummm57.3663.1279.39

c) Minimummm52.9560.4073.33
iv)Minimum breaking load




a) Before strandingKN9.2910.4312.85

b) After strandingKN8.839.9112.22
v)Elongation of 200 mm length on breaking%444
vi)Coating of steel core




a) Quality of Zinc
99.95%
purity
99.95%
purity
As per IS: 209-1979

b) Process of galvanising
Hot DipHot DipHot Dip

c) Minimum weight of coatinggm/m2240250260

d) Minimum no of dips of one minute duration which the strand can withstand (under preace test)Nos.333
7.Particulars of Complete Conductor



i)Code words, if any
ACSR 'Panther'ACSR 'Zebra'ACSR 'Moose'
ii)Copper equivalent Areamm2310260325
iii)Nominal aluminium areamm2200420520
iv)Sectional area of aluminiummm2212.10428.91528.50
v)Total sectional areamm2261.50484.50597.00
vi)Overall diametermm21.0028.6231.77
vii)Stranding, lay and wire diameter




a) Aluminiummm30/3.00 Right
Hand lay
54/3.1854/3.53

b) Steelmm7/3.007/3.187/3.53
viii)Lay ratioMin. mMaxm



a) Steel core




i) 6 wire LayerMax.282828


Min.131316

b) Aluminium




i) 12 Wire Ist LayerMax.161514


Min.101012

ii) 18 Wire IInd layerMax.141413


Min.101011

iii) 24 Wire IIIrd LayerMax.-1212


Min.-1010
x)Approximate calculated breaking loadKN89.67130.32159.60
xi)Final modules of Elasticity (Practical)GN/m2806969
xii)Coefficient of linear expansionPer0C17.8x10-6193x10-619.35x10-6
xiii)Approximate total weight per Km




a) Steel SectionKg388.00437.00537.00

b) Aluminium SectionKg586.001184.001461.00

c) ACSR CompositeKg974.001621.001998.00
xiv)Calculated D.C. resistance at 200C (Maximum)Ohm/Km0.13900.068850.25595
xv)Standard length of conductor (with tolerance, if any)Metres1500+5%1500+5%1500+5%
xvi)Number of standard length in one reel (drum)NosOneOneOne
xvii)Random lengths (Maximum percentage of the lengths ordered)%101010